Growatt Error 300 (AC Voltage Out of Range)

Disclaimer: This content is for informational and educational purposes only. The diagnostic steps described are suggestions, not an official service manual.

Phenomenon: The inverter displays Error 300 on the screen or app, with the fault LED illuminated. The inverter disconnects from the grid and enters reconnection delay.

Technical Causes:

  • Grid voltage exceeds the permissible range defined by the selected safety standard.
  • Voltage rise due to high export and AC cable impedance.
  • Incorrect safety standard configuration.

Diagnostic Procedure:

  • Measure AC voltage at inverter terminals during the fault.
  • Compare against limits of the active safety standard.
  • Check for grid fluctuations or local impedance issues.

Resolution:

  • Wait for grid voltage stabilization.
  • Adjust safety standard or voltage limits if allowed by regulations.
  • Optimize AC cabling or reduce export if impedance-related.

WARNING: Maintenance and repair of PV systems, high-voltage DC, and AC components must only be performed by certified professionals with valid electrical qualifications (e.g., SEP/G1 in Poland, or local European equivalents). Unauthorized opening of the inverter housing will void the warranty and carries a risk of electric shock or fire.